• Addressable conventional technology
• Maximum temperature 78°C
• Individual detector addressing by
means of optional address module
• Optional connection of remote
indicator
• Sealed electronics
Description
The Thermal ROR Detector GD-55000-127 reacts to means of the optional Address Module NG60-1, each
temperature changes within defined periods of time, detector can be addressed individually. With that, the
up to a maximum temperature of 78°C. The intelligent activated detector can also be safely identified directly
evaluation of these data allows the early detection of on the control panel.
spreading fires. The detector complies with Class BR
and can be used up to a room height of 6m.
The detector can be attached to various bases and it
can be protected against theft.
Addressable conventional technology is used for alarm
transmission to the fire detection control panel. By
Specifications
Operating voltage
Current consumption
Alarm temperature
Operating temperature
Ambient temperature
Relative humidity
Dimensions ø × H
Colour
Supply through the detector line voltage
typ. 45µA (quiescent)
78°C (maximum-heat component)
max. +65°C
-20°C to +90°C (no condensation or icing)
0 – 95% (no condensation)
100 × 42 (mm)
white
Weight
80g
Approval
VdS G200060
Order number
Order name
242025
Thermal ROR Detector/Conv./65/Apo GD-55000-127
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
GD-55000-127_DBL_LST_EN_0804.PDF • PAGE 1
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
|
Learning Resources Baby Toy ler5404 User Manual
Leica Laser Level 776748 User Manual
Lenovo Personal Computer Q180 Series User Manual
LG Electronics Stereo System LX M150 User Manual
Lincoln Automobile 2007 Navigator User Manual
Logitech Mouse M305 User Manual
Maytag Washer MAH7500 User Manual
Maytag Washer W10176966C User Manual
Melissa Kitchen Grill 643 096 User Manual
Microsoft Cell Phone OMPB20VWM User Manual